Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
166
05/2014
Table 87: UL 489 Listed, Drawout Automatic Switches
Frame Rating
Model
Number
Withstand Rating
1
1
The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit
breaker with an equal continuous current rating.
Instantaneous Override
240 V 480 V 600 V
4000 A
NW40HF 100 kA 100 kA 85 kA 75 kA
NW40HB
2
2
Not available in 4P.
1200 kA 150 kA 100 kA 75 kA
5000 A
NW50HF 100 kA 100 kA 85 kA 75 kA
NW50HB
2
200 kA 150 kA 100 kA 75 kA
6000 A
NW60HF 100 kA 100 kA 85 kA 75 kA
NW60HB
2
200 kA 150 kA 100 kA 75 kA
Table 88: IEC 60947-3 Rated, Non-Automatic Switches
Frame Rating
Model
Number
Interrupting Rating
1
1
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Short-Time (0.5 s)
Rating
240 V 440 V 690 V
4000 A NW40BHA 85 kA 85 kA 85 kA 85 kA
5000 A NW50HA 85 kA 85 kA 85 kA 85 kA
6300 A NW63HA 85 kA 85 kA 85 kA 85 kA